M thermal Mono       
82    202005 
Midea M thermal Mono Engineering Data Book 
5  DIP Switch Settings 
DIP switches S1 and S2 on the hydronic system main PCB should be used to specify refrigerant piping length and to specify 
whether certain  components  have or have  not been installed. Refer  to Table  3-5.1 and  to the M thermal Mono  Service 
Manual, Part 4, 2.2 "Main PCB for Hydronic System". 
 
Table 3-5.1: DIP switch settings 
00=Without IBH and AHS 
10=With IBH 
01=With AHS for heating mode 
11=With AHS for heating mode 
heating and DHW 
Start pumpo after   
six hours will   
be invalid 
Start pumpo after 
six hours will   
be valid 
00=variable speed pump   
(Max head:8.5m,Grundfos) 
01=constant speed pump   
(WILO) 
10= variable speed pump 
(Max head:10.5m,Grundfos) 
11=variable speed pump 
(Max head:9.0m, WILO) 
 
6  Internal Circulation Pump   
The  pump  is  controlled  via  a  digital  low-voltage  pulse-width modulation  signal which means that  the  speed  of  rotation 
depends on the input signal. The speed changes as a function of the input profile. The relationship between external static 
pressure and water flow rate is described in Part 2, 7 “Hydronic Performance”. 
 
Figure 3-6.1: Internal circulation pump