M thermal Mono       
88    202005 
Midea M thermal Mono Engineering Data Book 
PUMP tab on the DOMESTIC HOT WATER (DHW) menu, if TIMER RUNNING is enabled. 
 
DHW PUMP DI RUN sets wether or not the DHW pump (field supply) operates during the disinfection mode. 
 
7.5  COOL MODE SETTING Menu 
MENU > FOR SERVICEMAN > COOL MODE SETTING 
 
Figure 3-7.10: COOL MODE SETTING menu 
In COOL MODE SETTING the following parameters should be set. 
 
COOL MODE enables or disables cooling mode. For installations with space cooling terminals, select YES to enable cooling 
mode. For installations without space cooling terminals, select NON to disable cooling mode.   
 
t_T4_FRESH_C sets the refresh time of cooling model climate temperature curve. 
 
T4CMAX  sets  the  ambient  temperature  above  which  the  heat  pump  will  not 
operate in cooling mode. The highest value that T4CMAX can take is 46°C, which is 
the  cooling  mode  upper  ambient  temperature  operating  limit  of  the  heat  pump. 
Refer to Figure 3-7.11. 
 
T4CMIN sets the ambient temperature below which the heat pump will not operate 
in cooling mode. The lowest value that T4CMIN can take is -5°C, which is the cooling 
mode lower ambient temperature operating limit of the heat pump. Refer to Figure 3-7.11. 
 
dT1SC sets the minimum temperature difference between the heat pump leaving 
water temperature (T1) and the heat pump leaving water set temperature (T1S) 
at  which  the  heat  pump  provides  chilled  water  to  the  space  cooling  terminals. 
When  T1  –  T1S  ≥  dT1SC  the  heat  pump  provides  chilled  water  to  the  space 
cooling  terminals  and  when  T1  ≤  T1S  the  heat  pump  does  not  provide  chilled 
water to the space cooling terminals.   
 
dTSC sets the temperature difference between the actual room temperature (Ta) 
and  set  room  temperature  (TS)  above  which  the  heat  pump  provides  chilled 
water  to  the  space  cooling  terminals.  When  Ta  –  TS  ≥  dTSC  the  heat  pump 
provides chilled water to the space cooling terminals and when Ta ≤ TS the heat 
pump  does  not  provide  chilled  water  to  the  space  cooling  terminals.  Refer  to 
Figure 3-7.13. dTSC is only applicable if YES is selected for ROOM TEMP in the TEMP. TYPE SETTING menu. Refer to Part 3, 
7.8 “TEMP. TYPE SETTING Menu”. 
 
t_INTERVAL_C sets the cooling mode compressor re-start delay. When the compressor stops running, it will not re-start 
until at least t_INTERVAL_C minutes have elapsed.   
43°C
20°C
5°C
2.0HRS
YES
1/3
2 COOL MODE SETTING
2.1 COOL MODE
2.2 t_T4_FRESH_C
2.3 T4CMAX
2.4 T4CMIN
2.5 dT1SC
ADJUST
2°C
5MIN
10°C
16°C
35°C
2/3
2 COOL MODE SETTING
2.6 dTSC
2.7 t_INTERVAL_C
2.8 T1SetC1
2.9 T1SetC2
2.10 T4C1
ADJUST
25°C
FCU
FLH
3/3
2 COOL MODE SETTING
2.11 T4C2
2.12 ZONE1 C-EMISSION
2.13 ZONE2 C-EMISSION
ADJUST
Figure 3-7.11: T4CMAX, T4CMIN 
Abreviations: 
T4: Outdoor ambient temperature 
Abreviations: 
T1: Heat pump leaving water temperature 
T1S: Heat pump leaving water set temperature