CBFPCBFP - Circuit Breaker Failure Protection
This switch enables or disables the circuit breaker failure protection
feature. During a fault condition, TS2 output is activated in an attempt to
clear the fault. If after a prefixed delay time has lapsed, the fault remains
despite the activation of TS2 and this CBFP switch option is enabled, TS1
will be activated. Please note that if this feature is enabled, the settings in
Switch Group 3 will be overridden.
1 = Circuit breaker failure protection feature enabled
0 = Circuit breaker failure protection feature disabled
ILATCHILATCH - Overcurrent Latching Output
If this switch is set, an overcurrent trip will latch the relay output TS2.
Otherwise, the relay output TS2 will reset once the fault is cleared. Please
note that only the relay output is reset, the display remains in tripped
condition.
1 = Overcurrent trip will latch TS2 output.
0 = No latching of TS2 relay output.
ELATCH ELATCH - Earth-Fault Latching Output
If this switch is set, an earth-fault trip will latch the relay output TS2.
Otherwise, the relay output TS2 will reset once the fault is cleared. Please
note that only the relay output is reset, the display remains in tripped
condition.
1 = Earth-fault trip will latch TS2 output.
0 = No latching of TS2 relay output.
REMOTE REMOTE - Remote Reset
If either or both ILATCH and ELATCH are set to 1, trip reset can be done by a
remote signal from the digital input
1 = Remote reset feature enabled.
0 = No remote reset.