25
Position)
5523
Longitude: 9cff0807=>07 08 ff
9c=118030236/1000000=118.
030236
22=in motion
3. Distance Threshold: report when distance reaches the threshold or returns back to normal
value. If the threshold triggering time is close to periodic report time, it will send with periodic
uplink.
8482330701
Channel
Type
Value
84
82
(Distance)
Distance: 33 07 =>07 33 = 1843mm = 1.843m
01= Alarm
4. Temperature Threshold: report once when the abrupt change of temperature is greater than
5 °C.
8367220101 0688FFFFFFFFFFFFFFFF20
Channel
Type
Value
Channel
Type
Value
83
67
(Temperatu
re)
Temperature: 22 01
=>01 22 = 290 * 0.1
= 29 °C
01= Alarm
06
88(Locati
on)
Latitude/longitude
: FFFFFFFF
20=unknown
6.2.3 Downlink Commands
EM400-MUD supports downlink commands to configure the device. Note that it can only receive
downlink commands within the 10s after sending uplink packets.
Channel
Type
Description
ff
10 (Reboot)
ff (Reserved)
03 (Reporting Interval)
4 Bytes, unit: s
71 (Device Mode)
00 = Standard Mode; 01 = Bin Mode
3e (Tilt & Distance Switch)
00 = Disable; 01 = Enable
a0 (Position Setting)
00 = Disable; 01 = Enable
58 (Duration of Motion and
Stationary)
5 Bytes,
Byte 1: duration of motion, unit: s
Byte 2-5: duration of stationary, unit: s
8e (Motion Report Interval)
5 Bytes,
Byte 1: 00 = Disable; 01 = Enable
Byte 2-5: report interval, unit: s