Default: 200 s, Range: 1-3600 s
Import the client certificate.
After TCP/UDP connection established, the device will send one package
including the description to identify the device. The max length is 32
characters.
For TCP connection, the device will send heartbeat packet regularly to keep
alive. Default: 60 s, Range: 60-7200 s
After enabled, the device will send custom heartbeat packets to TCP server.
Customize the heartbeat packet content. The max length is 32 characters.
The device will send custom heartbeat packet regularly. Default: 30 s, Range:
30-3600 s
After the device send custom heartbeat packet, it needs a specific response
from server.
Customize the server reply content after receiving custom heartbeat packets.
The max length is 32 characters.
Fill in the TCP/UDP server address (IP/domain name).
Fill in the TCP/UDP server port. Range: 1-65535.
Note: The server address and port should not exactly the same as the
TCP/UDP settings on “RS232” page.
Show the connection status between the device and the server.
Fill in MQTT broker address to receive data.
Fill in MQTT broker port to receive data.
Client ID is the unique identity of the client to the server, it must be unique
when all clients are connected to the same server.
After the client is connected with the server, the client will send heartbeat
packet regularly to keep alive. Default: 60 s, Range: 1-65535 s
The username used for connecting to MQTT broker.