ALTERING PARAMETER VALUES
With
[P# #] displayed, the operator may elect to change the contents of the selected parameter. Key in the
desired value and press
"ENTER". If the operator fails to press "ENTER" after keying in a new parameter
value, the original value will be retained. If the parameter value altered was in the APA loop pressing
"ENTER"
again will cause the next parameter in the loop to be accessed.
e.g.
[P02 1] is displayed, option 2 is desired
press
"2"
[P02 2]
is displayed
press
"ENTER"
PARAMETER RESET
This feature returns the Compu-M memory to factory settings. The implementation of a reset: requires total
parameter re-entry, zero and span recalibration, and resets the local totalizer to 0. Refer to Parameter Listing
P99 for details.
DISPLAY MESSAGES
Display Message Comment
[ E1 ] security code required refer to P66
[ E2 ] total registration too low enter a higher value in P2 or P3
[ E3 ] zero out of range zero deviation is greater than limit as set by P-25
[ E4 ] span out of range deviation from initial span is greater than 12.5% of span
[ E5 ] parameter not entered a required parameter was not entered during the initial programming
[ E6 ] zero calibration required perform a zero calibration. By-pass by pressing "CLEAR " "ENTER",
if a zero recalibration has been performed recently.
[ E7 ] span calibration required perform a span calibration
[ E8 ] entry error invalid parameter number entered
invalid parameter value entered
[ E9 ] auto zero out of range self initiated auto zero deviation from the last routine zero is greater
than 2% but less than 12.5% of span
PL-516 25