START UP
GENERAL
The MultiRanger Plus has two modes of operation: Run and Program (Cal). When
the unit is powered up, after installation procedures have been completed, it is factory
set to start up in the run mode, to detect the distance from the transducer face to the
target in meters. This is the normal mode of operation, which can be programmed to
display level, volume, totals or flow readings and yield corresponding mA output and
relay closures for alarms, pump controls, etc.
The program mode is selected by pressing the
Run/Cal
key. This mode will enable
the user to program the MultiRanger Plus to suit his preference and to the particular
application to which the MultiRanger Plus is being applied.
The first step when programming is to reset all parameters to their
factory setting by using the master reset P-99
After having entered all required parameters, the MultiRanger Plus can be made to
simulate its operation within the particular application giving display, relay operation
and analog output. Refer to parameters P-76 through P-78.
When programming has been completed, the MultiRanger Plus can be put into normal
operation by pressing the
Run/Cal
key.
PL-443 4 – 1