SPECIFICATIONS
MULTIRANGER PLUS
Power: » 100/115/200/230 V ±15%, stab selective
» 50/60 Hz, 15 VA
» optional: » 12 V dc model, 10 to 18 V dc
» 24 V dc model, 18 to 36 V dc
Fuse: » 1/4 amp MDL Slo-Blo or equivalent
Range: » 0.3 to 15 m (1 to 50 ft)
Accuracy: » 0.25% of range or 6 mm (0.24"), whichever is greater
Resolution: » 0.1% of range or 2 mm (0.08"), whichever is greater
Memory: » EEPROM (non-volatile) no back-up battery required
Display: » Liquid Crystal Display of 4 digits, 18mm (0.7") high
Operating Temperature: » – 20 to 60 °C (– 5 to 140 °F)
Outputs: transducer drive: » 41 KHz, 400 V peak pulses of 1 msec
max duration at a max
repetition rate of 300 msec
analog: » 0 - 20 or 4 - 20 mA
» max loading: » 350 ohms, return to ground
» 750 ohms, return to –12 V
» resolution: 0.1% of range
» optional mA isolator
relays: » 5 multipurpose relays (for alarms, pump control,...)
» 1 Form "C" SPDT contact per relay, rated 5 A at
220 V ac non-inductive
» adjustable deadband
All relays are certified for use in equipment where the short
circuit capacity of the circuits in which they are connected is
limited by fuses having ratings not exceeding the rating of the relays.
Enclosure: » CSA enclosure type 4 (similar to NEMA 4)
» 160 mm W x 250 mm H x 82 mm D
(6.3" W x 9.5"H x 3.2"D)
» polycarbonate
Approvals: » CE
Weight » 1.8 kg (4lb)
96/01/22
PL-443 2 – 1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Milltronics MultiRanger Plus and is the answer not in the manual?

Milltronics MultiRanger Plus Specifications

General IconGeneral
BrandMilltronics
ModelMultiRanger Plus
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals