Pump Control Example
The application is to control the level in a wet well 3 meters deep. It is required that :
» the level is displayed in meters
» to start/stop two constant speed pumps: start pump 1 at 1 m level
start pump 2 at 2 m level
stop both pumps at 0.5 m level
» the two pumps operate on a cumulative sequential loop, de-energized
under loss of echo
» low alarm is set at 0.4 m to protect the two pumps from cavitating
» the transducer is mounted 3.4 meters from the bottom of the wet well
» the span of level in the well is 3 m
» maximum fill rate is 1m / min, maximum draw rate is 0.2 m / min
» in the event of loss of echo, go into fail-safe low after 30 seconds to
protect pumps
» the transducer is the submersible type as there is a possibility of flooding
select :
P-1 enter option "1", units in meters
advance to:
P-2 enter option "1", material level
P-3 enter "3.3", empty distance to transducer
P-4 enter "3", span
P-5 enter "
.300", blanking distance, ( use factory setting )
P-7 enter "2", display max 2 digits after decimal
P-8 enter option "dE 9" relay 1 - pump function
(press "9" and
then "
*
" until "dE 9"
is displayed)
P-9 enter "1", relay 1 - pump ON
P-10 enter "
.5", relay 1 - pump OFF
P-11 enter option "dE 9" relay 2 - pump function
(press "9" and
then "
*
" until "dE 9"
is displayed)
PL-443 6 – 7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Milltronics MultiRanger Plus and is the answer not in the manual?

Milltronics MultiRanger Plus Specifications

General IconGeneral
BrandMilltronics
ModelMultiRanger Plus
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals