Conditions of use : » Do not use run-on feature during pump-up operation as
an overflow condition may occur. Set P-29 and 30 to 0.
» Select the loss of echo default "dE" to protect pumps
from cavitating in the event of loss of echo
» The run-on interval must be greater that the run-on duration.
e.g. P-29 = 24 and P-30 = 15
After 24 hours from going into the run mode, the MultiRanger Plus
enters the second run-on interval allowing only one pump run-on
cycle of 15 seconds, at the first time the lead pump turns off. If the
lead pump turns off a second time during that 24 hour interval, no
run-on will occur. After the 24 hour interval has elapsed, whether a
pump run-on has occurred or not, the next run-on interval will begin,
allowing one run-on cycle.