Apx.A
Use one-pair wiring for an N:N Network.
Terminal
resistor:
110
Class-D grounding
(resistance: 100 or less)
*1
Class-D grounding
(resistance: 100 or less)
*1
FX
2NC
-485ADP
SDA
(TXD+)
SDB
(TXD-)
RDA
(RXD+)
RDB
(RXD-)
SG
FX
3G
-485-BD
FX
3U-485-BD
FX
2N
-485-BD
FX
1N
-485-BD
FX
3U
-485ADP(-MB)
FX
3G
-485-BD
FX
3U-485-BD
FX
2N
-485-BD
FX
1N
-485-BD
FX
3U
-485ADP(-MB)
SDA
(TXD+)
SDB
(TXD-)
RDA
(RXD+)
RDB
(RXD-)
SG
FX
0N
-485ADP
SDA
(TXD+)
SDB
(TXD-)
RDA
(RXD+)
RDB
(RXD-)
LINK
SG
FG
*2
Terminal
resistor:
110
SDA
(TXD+)
SDB
(TXD-)
RDA
(RXD+)
RDB
(RXD-)
SG
*3 *3
Make sure to perform Class-D grounding on the shield of a twisted pair cable connected to the FX2N-485-BD, FX1N-485-BD,
FX
3U-485-BD, FX3G-485-BD, FX2NC-485ADP or FX3U-485ADP(-MB).
FG
Make sure to connect the terminal to the (grounding) terminal in the PLC requiring Class-D grounding.
If the grounding terminal is not provided in the PLC, perform Class-D grounding directly.
Make sure to provide a terminal resistor at the end of each line.
The FX
3U-485-BD, FX3G-485-BD and FX3U-485ADP(-MB) have a built-in terminal resistor. Set the terminal resistor selector
switch accordingly.
The FX
0N
-485ADP, FX
2NC
-485ADP, FX
2N
-485-BD and FX
1N
-485-BD are supplied together with terminal resistors.