C-31
FX Series PLC User's Manual - Data Communication Edition
Parallel Link
4 Wiring
4.4 Grounding
A
Common Items
B
N:N Network
C
Parallel Link
D
Computer Link
E
Inverter
Communication
F
Non-Protocol
Communication
(RS/RS2 Instruction)
G
Non-Protocol
Communication
(FX
2N
-232IF)
H
Programming
Communication
I
Remote
Maintenance
Apx.A
Discontinued
models
2. In the case of two-pair wiring
*1. Make sure to perform Class-D grounding on the shield of a twisted pair cable connected to
the FX
2N-485-BD, FX1N-485-BD or FX2NC-485ADP.
*2. Make sure to connect the terminal to the (grounding) terminal in the PLC requiring
Class-D grounding.
If the grounding terminal is not provided in the PLC, perform Class-D grounding directly.
4.3.3 For FX2(FX) and FX2C PLCs
*1. Connect the terminal to the terminal in each PLC (main unit).
4.4 Grounding
Grounding should be performed as stated below.
• The grounding resistance should be 100 or less.
• Independent grounding should be performed for best results.
When independent grounding can not be performed, perform "shared grounding" as shown in the following
figure.
For details, refer to the Hardware Edition of each series.
• The grounding wire size should be AWG 14 (2 mm
2
) or larger.
• The grounding point should be close to the PLC, and all grounding wires should be as short as possible.
Class-D grounding (resistance: 100 or less)
*1
SG
FX
2NC
-485ADP
FX
2N
-485-BD
FX
1N
-485-BD
SG
SDA
(TXD+)
SDB
(TXD-)
RDA
(RXD+)
RDB
(RXD-)
SG
FX
2NC
-485ADP FX
0N
-485ADP
LINK
SG
FG
*2
FX
2N
-485-BD
FX
1N
-485-BD
SG
FX
0N
-485ADP
SDA
(TXD+)
SDB
(TXD-)
RDA
(RXD+)
RDB
(RXD-)
SDA
(TXD+)
SDB
(TXD-)
RDA
(RXD+)
RDB
(RXD-)
LINK
SG
FG
Terminal
resistor
330
2
Terminal
resistor
330
2
SDA
(TXD+)
SDB
(TXD-)
RDA
(RXD+)
RDB
(RXD-)
SDA
(TXD+)
SDB
(TXD-)
RDA
(RXD+)
RDB
(RXD-)
SDA
(TXD+)
SDB
(TXD-)
RDA
(RXD+)
RDB
(RXD-)
SA
SB
SG
*1
FX
2
-40AW FX
2
-40AW
SA
SB
SG
*1
FX
2
-40AP
T
R
FX
2
-40AP
R
T
PLC
Other
equipment
PLC
Other
equipment
PLC
Other
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition