4 - 14
REPLACEMENT OF THE MELSECNET/10 (PLC TO PLC NETWORK)
4
: Compatible, : Partial change required, ×: Incompatible
*1 The QnA/QnAS series support the loop test.
4.4 Switch Settings Comparisons
Switch name
Description
Compat-
ibility
Precautions for replacement
A/AnS/QnA/QnAS series
MELSECNET/10 module
Q series
MELSECNET/H module
(MELSECNET/10 mode)
Network No.
setting switch
Sets the network No. -
Set in GX Works2 or GX
Developer network
parameters.
Network No.240 to No.255
cannot be set.
Alternate them with unused
network Nos.
Group No.
setting switch
Sets the group No. -
Set in GX Works2 or GX
Developer network parameters.
Mode setting
switch
Sets the mode.
<Setting range>
0: Online
2: Offline
3: Loop test (forward loop)
*1
4: Loop test (reverse loop)
*1
5: Station-to-station test
(master station)
6: Station-to-station test
(slave station)
7: Self-loopback test
8: Internal self-loopback test
9: H/W test
D: Network No. check
E: Group No. check
F: Station No. check
Sets the mode.
<Setting range>
0: Online
1: Self-loopback test
2: Internal self-loopback test
3: hardware test
Set offline, loop test and
station-to-station test in GX
Works2 or GX Developer
network parameters.
Check network No., group
No. and station No. in GX
Works2 or GX Developer
network diagnostics (host
information).
Condition setting
switch
Sets the operation conditions. -
This switch cannot make
parameter setting.
Set in GX Works2 or GX
Developer network parameters.