6 - 12
REPLACEMENT OF CC-LINK
6
6.6.1 Comparison of I/O signals
(1) A/AnS series
(a) Input signal
: Compatible, : Partial change required, × : Incompatible
6.6 Program Comparisons
Input signal
Signal name
Compat-
ibility
Precautions for replacement
AJ61BT11/A1SJ61BT11 QJ61BT11N
Xn0 Module error Module error
Xn1 Data link status at host station Data link status at host station
Xn2 Parameter setting status Prohibited to use
Delete the sequence program of the section
corresponding to the function, and check with
SB006D (Parameter setting status).
Xn3 Data link status of other station Data link status of other station
Xn4
Module reset acceptance
complete
Prohibited to use ×
Delete the sequence program of the section
corresponding to the function.
When the switch setting is changed, turn the power
supply of programmable controller system OFF
ON or reset the programmable controller CPU.
Xn5 Prohibited to use Prohibited to use
Xn6
Data link startup by buffer
memory parameter normal
completion
Prohibited to use
Delete the sequence program of the section
corresponding to the function, and set parameters
with GX Works2/GX Developer or with dedicated
instruction (RLPASET instruction).
Xn7
Data link startup by buffer
memory parameter error
completion
Xn8
Data link startup by E
2
PROM
parameter normal completion
Xn9
Data link startup by E
2
PROM
parameter error completion
XnA
Parameter registration to
E
2
PROM normal completion
XnB
Parameter registration to
E
2
PROM error completion
XnC Prohibited to use Prohibited to use
XnD
E
2
PROM erasure normal
completion
Prohibited to use
Delete the sequence program of the section
corresponding to the function, and set parameters
with GX Works2/GX Developer or with dedicated
instruction (RLPASET instruction).
XnE
E
2
PROM erasure abnormal
completion
XnF Module ready Module ready
X(n+1)0
Prohibited to use Prohibited to use
X(n+1)1
X(n+1)2
X(n+1)3
X(n+1)4
X(n+1)5
X(n+1)6
X(n+1)7
X(n+1)8
X(n+1)9
X(n+1)A
X(n+1)B
X(n+1)C
X(n+1)D
X(n+1)E
X(n+1)F