REPLACEMENT OF CC-LINK
6 - 11
6
(1) A/AnS series
: Compatible, : Partial change required, × : Incompatible
(2) QnA/QnAS series
: Compatible, : Partial change required, × : Incompatible
*1 Parameter setting of Q series CC-Link modules
Parameters can be set on up to eight modules using GX Works2 or GX Developer. For the settings of the 9th module or
later, use the dedicated instruction.
For details, refer to the CC-Link System Master/Local Module User's Manual.
*2 Delete the program for the network parameter setting of the existing module.
6.5 Parameter Comparisons
Parameter name
Specifications Compat-
ibility
Precautions for
replacement
AJ61BT11/A1SJ61BT11 QJ61BT11N
Network parameter
Set this parameter with the
sequence program (TO
instruction) or with dedicated
instruction (RLPA instruction).
Set this parameter with GX
Works2/GX Developer or with
dedicated instruction
(RLPASET instruction).
Newly set the parameter
with GX Works2/GX
Developer or the dedicated
instruction (RLPASET
instruction).
*1 *2
Specify [Remote net Ver.1
mode] or [Remote I/O net
mode] for the mode.
Automatic refresh
parameter
Read/write cyclic data with
FROM/TO instruction or set
this parameter with dedicated
instruction (RRPA instruction).
Perform the automatic refresh
setting with GX Works2/GX
Developer or read/write cyclic
data with FROM/TO
instruction.
Perform the automatic
refresh setting with GX
Works2/GX Developer or
read/write cyclic data with
FROM/TO instruction.
When setting the network
parameter with dedicated
instruction (RLPASET
instruction), read/write
cyclic data with FROM/TO
instruction.
Parameter name
Specifications Compat-
ibility
Precautions for
replacement
AJ61QBT11/A1SJ61QBT11 QJ61BT11N
Network parameter
Set this parameter with GX
Developer or sequence
program (TO instruction).
Set this parameter with GX
Works2/GX Developer or with
dedicated instruction
(RLPASET instruction).
Newly set the parameter
with GX Works2/GX
Developer or the dedicated
instruction (RLPASET
instruction).
*1 *2
Specify [Remote net Ver.1
mode] or [Remote I/O net
mode] for the mode.
Automatic refresh
parameter
Perform the automatic refresh
setting with GX Developer or
read/write cyclic data with
FROM/TO instruction.
Perform the automatic refresh
setting with GX Works2/GX
Developer or read/write cyclic
data with FROM/TO
instruction.
Set the automatic refresh
with GX Works2/GX
Developer or read/write
cyclic data with FROM/TO
instruction.
When setting the network
parameter with dedicated
instruction (RLPASET
instruction), read/write
cyclic data with FROM/TO
instruction.