REPLACEMENT OF MELSECNET (II) AND /B (PLC TO PLC NETWORK)
2 - 13
2
2.5.2 Example of changing parameters on 2-tier system
The following shows examples of how to change the LB/LW network parameters when replacing the
MELSECNET (II) with MELSECNET/H.
As MELSECNET (II) has three operation modes, the examples are shown for each operation mode.
• MELSECNET mode
• MELSECNET II mode
• MELSECNET II composite mode
(1) MELSECNET mode
The following shows the procedure for changing the parameters in the case of a MELSECNET mode 2-
tier system configuration.
The MELSECNET master station is replaced with the MELSECNET/H control station, and MELSECNET
local stations are replaced with MELSECNET/H normal stations.
A MELSECNET/H module set as normal station requires network parameter setting. For replacement of
MELSECNET (II) module mounted on the CPU module of the AnN/AnA/AnSCPU (excluding
AnUS(H)CPU), newly set network parameters.
The following shows parameters required on each station of MELSECNET/H.
: Setting required/ : Setting required (Default setting is also acceptable)
MELSECNET MELSECNET/H
Optical loop
(Link parameter setting range)
Optical loop
Common parameter
(Network range assignment)
Refresh parameter
1Mp1
(Refer to example in (c) 2)) (Refer to example in (c) 3))
1Ns2
(Refer to example in (d) 2))
1Ns3
(Refer to example in (d) 2))
1Ns4
(Refer to example in (d) 2))
L3L1
M
L2
A3ACPU
A2ACPU
EmptyL3
B/W 0 100 200 3FF380300
M L1 L2
Network
1
1N
S41NS2
1M
P1
1N
S3
Q06UDVCPU
Q02UCPU