6.6.2 Buffer memory comparisons
(1) A/AnS series
Buffer memory is divided into bank0 to bank2 on the A/AnS series, but it is one area on the Q series.
Bank is switched with ON/OFF of Y (n+1)C, Y(n+1)D.
Buffer memory address of the Q series is shown in parenthesis, as buffer memory addresses of
communication buffer and automatic updating buffer are different.
: Compatible, : Partial change required, × : Incompatible
Buffer memory address Buffer memory name
Compat-
ibility
Precautions for
replacement
Bank Hex. Dec. AJ61BT11/A1SJ61BT11 QJ61BT11N
0
0H to 5FH 0 to 95
Parameter information
area
Parameter information
area
60
H to 7FH 96 to 127 Prohibited to use Prohibited to use
80
H to CDH 128 to 205
Parameter information
area
Parameter information
area
CE
H to DFH 206 to 223 Prohibited to use
Parameter information
area
Added with the remote net
Ver.2 mode.
Replacement is not applied.
E0
H to 15FH 224 to 351 Remote input (RX) Remote input (RX)
160
H to 1DFH 352 to 479 Remote output (RY) Remote output (RY)
1E0
H to 2DFH 480 to 735 Remote register (RWw) Remote register (RWw)
2E0
H to 3DFH 736 to 991 Remote register (RWr) Remote register (RWr)
3E0
H to 5DFH 992 to 1503 Prohibited to use
Slave station offset, size
information
Added with the remote net
Ver.2 mode.
Replacement is not applied.
5E0
H to 5FFH 1504 to 1535 Link special relay (SB) Link special relay (SB)
600
H to 7FFH 1536 to 2047 Link special register (SW) Link special register (SW)
800
H to 9FFH 2048 to 2559 Prohibited to use Prohibited to use
A00
H to FFFH 2560 to 4095 Random access buffer Random access buffer
1
0 to FFF
H
(1000H to 1FFFH)
0 to 4095
(4096 to 8191)
Communication buffer Communication buffer
Delete the program for bank
switching.
2
0 to FFF
H
(2000H to 2FFFH)
0 to 4095
(8192 to 12287)
Automatic updating buffer Automatic updating buffer
Delete the program for bank
switching.
-
-
(3000
H to 3FFFH)
-
(12288 to 16383)
-
Prohibited to use -
-
-
(4000
H to 53FFH)
-
(16384 to 21503)
Area for Ver.2
The function was added to Q
series modules.
-
-
(5400
H to 7FFFH)
-
(21504 to 32767)
Prohibited to use -
Q series
0
H
2FFF
H
A/Ans series
Bank 1 Bank 2
0
H
FFF
H
0
H
FFF
H
0
H
FFF
H
Bank 0
Y(n+1)C : OFF
Y(n+1)D : OFF
Y(n+1)C : ON
Y(n+1)D : OFF
Y(n+1)C : OFF
Y(n+1)D : ON