EasyManua.ls Logo

Mitsubishi Electric Melsec A Series - Page 189

Mitsubishi Electric Melsec A Series
248 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 - 23
REPLACEMENT OF THE MELSECNET/10 (REMOTE I/O NETWORK)
5
(2) Remote I/O station switch settings comparisons
: Compatible, : Partial change required, × : Incompatible
*1 Modules with a serial number (first five digits) of "15012" or later supports Online (MELSECNET/10 mode).
Switch name
Description
Compat-
ibility
Precautions for replacementA/AnS/QnA/QnAS series
MELSECNET/10 module
Q series
MELSECNET/H module
Mode setting
switch
Sets the mode.
<Setting range>
0: Online
2: Offline
3: Loop test (forward loop)
4: Loop test (reverse loop)
5: Station-to-station test
(master station)
6: Station-to-station test
(slave station)
7: Self-loopback test
8: Internal self-loopback test
9: H/W test
F: Station No. check
[Using QJ72LP25-25]
Sets the mode.
<Setting range>
0: Online (10Mbps)
1: Self-loopback test (10Mbps)
2: Internal self-loopback test
(10Mbps)
3: Hardware test (10Mbps)
4: Online (25Mbps)
5: Self-loopback test (25Mbps)
6: Internal self-loopback test
(25Mbps)
7: Hardware test (25Mbps)
8: Online (MELSECNET/10
mode)
*1
Set offline and loop test in GX
Works2 or GX Developer
network parameters.
Substitute the forward loop/
reverse loop test for the station-
to-station test.
Check network No., group No.
and station No. in GX Works2 or
GX Developer network
diagnostics (host information).
[Using QJ72LP25G and
QJ72BR15]
Sets the mode.
<Setting range>
0: Online
1: Self-loopback test
2: Internal self-loopback test
3: Hardware test
8: Online (MELSECNET/10
mode)
*1
Condition
setting switch
Sets the operation conditions. -
Nothing to be noted for the
MELSECNET/H.

Table of Contents

Other manuals for Mitsubishi Electric Melsec A Series

Related product manuals