REPLACEMENT OF CC-LINK
6 - 5
6
(1) A/AnS series
: Compatible, : Partial change required, × : Incompatible
(To next page)
6.3 Functional Comparisons
Item
Specifications Compat-
ibility
Precautions for
replacement
AJ61BT11/A1SJ61BT11 QJ61BT11N
Communication
between master station
and remote I/O station
The communication of ON/OFF information with remote I/O
station is performed.
Communication
between master and
remote device stations
The communication of ON/OFF information and numerical data
with remote device station is performed.
Communication
between master station
and local station
The communication of ON/OFF information and numerical data
with local station is performed.
Communication
between master and
intelligent device
stations
The communication is performed with intelligent device station
using cyclic transmission and transient transmission.
Reserved station
function
By setting remote station and local station, which are to be
connected in the future, as reserved stations, these stations are
not treated as data link faulty stations.
If a connected module is specified, no data link is available.
Error invalid station
function
Remote station and local station that cannot perform data link
due to the power supply off, etc. will not be treated as data link
faulty stations with this function.
Data link status setting
at master station
programmable controller
CPU error
The data link status when operation continuation error occurs on
the master station programmable controller CPU can be set.
Parameter registration
to E
2
PROM
Parameter writing is not
required at each startup of
master module by registering
parameters to E
2
PROM of
master module.
-
GX Works2 or GX
Developer parameter
settings are performed
instead of the parameter
registration to E
2
PROM.
Data link faulty station
input data status setting
The input (received) data status (cleared/hold) from the station
that has data link error caused by the power supply off, etc. can
be set.
Module reset function by
sequence program
Resetting can be performed by
the sequence program without
resetting programmable
controller CPU in the case the
switch setting is changed or an
error has occurred in a module.
When the switch setting is
changed, turn the power
supply of programmable
controller system OFF
ON or reset the
programmable controller
CPU.
Data link stop/restart
The stop and restart of data link is available during the data link
execution.
Automatic return
function
The module disconnected from data link by the power supply off,
etc. can automatically return to data link, when restored to the
normal status.
Slave station detach
function
The module that cannot perform data link due to the power
supply off, etc. is disconnected and data link is kept with normal
modules only.
Data link status check
(SB/SW)
Data link status can be checked.
This check can be used for the interlock etc. of sequence
program.