REPLACEMENT OF CC-LINK
6 - 9
6
(1) A/AnS series
: Compatible, : Partial change required, × : Incompatible
6.4 Switch Settings Comparisons
Switch name
Specifications Compat-
ibility
Precautions for
replacement
AJ61BT11/A1SJ61BT11 QJ61BT11N
Station number setting
switch
Sets the station No. of the
module.
<Setting range>
For remote net mode
Master station: 0
Local station: 1 to 64
Standby master station: 1 to
64
For remote I/O net mode
Master station: 1 to 64 (The
last station No. of remote I/O
station is set.)
Sets the station No. of the
module.
<Setting range>
Master station: 0
Local station: 1 to 64
Standby master station: 1 to 64
Sets the last station No. at
remote I/O net mode with
GX Works2 or GX
Developer.
Mode setting switch
Sets the operation status of the
module.
Sets the transmission speed
and operating status of the
module.
The mode setting and the
transmission rate setting
are performed with one
switch.
The remote net mode and
remote I/O net mode are
specified in GX Works2 or
GX Developer parameter
settings.
Transmission speed
setting switch
Sets the transmission speed of
the module.
Condition setting switch
Sets the operation conditions.
<Settings>
Station type
Input data status of data link
faulty station
Number of occupied stations
Module mode
-
The operating conditions
are set in the parameter
settings of GX Works2 or
GX Developer.
Module mode setting is
not required.