6 - 22
REPLACEMENT OF CC-LINK
6
: Compatible, : Partial change required, × : Incompatible
Number
Name Compat-
ibility
Precautions for replacement
AJ61QBT11/A1SJ61QBT11 QJ61BT11N
SB0069 Module mode -
The mode is set on the Q series
using the network parameters.
(The setting can be checked in
SW0060.)
SB006F
-
Setting status of block
guarantee of cyclic data per
station
Added on the Q series and
replacement is not applied.
SB0079
Master station return
specification information
SB007B
Host master/standby master
operation status
SB007C
Slave station refresh/
compulsory clear setting status
in case of programmable
controller CPU STOP
SB00A0
RECV instruction (1) execution
request flag
-
Not used on the Q series.
Delete the sequence program
of the section corresponding to
the function.
SB00A1
RECV instruction (2) execution
request flag
SB00B4
-
Standby master station test
result
Added on the Q series and
replacement is not applied.
SB0184
Transmission speed test result
for standby master station
SB0185
Transmission speed test
accept status
SB0186
Transmission speed test
completion status