REPLACEMENT OF MELSECNET (II) AND /B (PLC TO PLC NETWORK)
2 - 19
2
(b) MELSECNET/H control station
Each of the MELSECNET II first and second half settings correspond to [Setting1] and [Setting2] set
according to the "Station inherent parameters" on MELSECNET/H.
1) Network parameter
The network parameter settings of the MELSECNET/H control station (Q06UDVCPU) are the
same as the parameters when replaced with the MELSECNET mode.
2) Network range assignment parameter
Set the total number of points in the first half and second half for the common parameters.
Points when replacing the first and second half of MELSECNET II
MELSECNET sequence programs can be re-used more efficiently by using the station inherent parameters of MELSECNET/H.
The followings describe the points when setting station inherent parameters.
• Set station inherent parameters to all stations.
Network parameter setting (Q06UDVCPU: MELSECNET/H control station)
Network range assignment (Q06UDVCPU: MELSECNET/H control station)