REPLACEMENT OF MELSECNET (II) AND /B (PLC TO PLC NETWORK)
2
Concept of MELSECNET II 3-tier system replacement
Step 1: Control station (1Mp3) setting
Set the link parameter setting on MELSECNET II 2-tier master station as MELSECNET/H network 1 control station 1Mp3.
In "Network range assignment (Common parameters)" of control station 1Mp3, set the LB/LW (first half size + second half size)
as a contiguous area on each station.
It is divided into the first half LB/LW and the second half LB/LW, and transferred depending on the settings 1 and 2 of "Station
inherent parameter".
Step 2: Common parameter and refresh parameter settings of gateway station (1Ns1/2Mp3)
"Common parameter" setting and "Refresh parameter setting" of the MELSECNET II 3-tier master station are set as
MELSECNET/H network 2 control station 2Mp3 and network 1 normal station 1Ns1.
In "Network range assignment (Common parameters)" of control station 2Mp3, set the LB/LW (first half size + second half size)
as a contiguous area on each station.
The range assignment should be performed including the same LB/LW size as that of 1Mp3 to relay 1Mp3.
Set "Refresh parameter" to transfer B/W by dividing it into the first half B/W and the second half B/W on each station of network
2 control station 2Mp3 and network 1 normal station 1Ns1.
Make sure that B/W of networks 1 and 2 will not duplicate on the CPU.
As "Interlink transmission parameters" parameter the gateway station 1Ns1/2Mp3 is set for, do not set a station inherent
parameter.
Step 3: Inter-link data transfer setting of gateway station (1Ns1/2Mp3)
Data transfer between 2 and 3-tier, which is performed automatically on MELSECNET II, is performed by Inter-link data transfer
on gateway station 1Ns1/2Mp3.
LB/LW area shared by networks 1 and 2 is set by "Interlink transmission parameters" parameter of gateway station between
1Ns1 and 2Mp3.
Step 4: Station setting other than gateway stations (1Ns2, 2Ns1, 2Ns2)
"Station inherent parameter" and "Refresh parameters" of stations excluding gateway stations (1Ns2, 2Ns1, 2Ns2) are set.
Set "Station inherent parameter" of network 1 normal station 1Ns2 as the same setting as that of network 1 control station
1Mp3.
Set "Station inherent parameter" of network 2 normal station 2Ns2 as the same setting as that of network 2 normal station
2Ns1.
Set "Refresh parameter" to refresh all area of common parameters assigned on control stations.