FX2NC Series Programmable Controllers Outputs 6.
6-13
6.3 Triac (SSR) output specifications
Table 6.8 :
Switched voltages (resistive load)
85-242V AC
Rated current / N points (resistive
load)
0.3A/1point, 0.8A/COM
Max. Inductive load
15VA/100V AC, 36VA/240V AC
Max. lamp load (tungsten load)
30W (0.35A/85V AC, 0.12A/242V AC)
Minimum load
0.4VA/100V AC, 2.3VA/240V AC
Open circuit current leakage
1mA/100V AC, 2.4mA/240V AC
Response time
(approx.)
OFF
ON
<1ms
ON
OFF
<10ms
Circuit isolation
by photocoupler
Operation indication
LED is lit when photocoupler is driven