FX2NC Series Programmable Controllers Installation notes 3.
3-4
3.2 FX
2NC
RUN/STOP Control
RUN or STOP of the FX
2NC
can be controlled by:
n
The RUN/STOP switch mounted next to the programming port.
o
A standard input (X000 to X017; X000 to X007 for FX
2NC
-16M
units) defined by the system
parameters.
p
Remotely from a personal computer or other programming peripheral.
Note
:The FX
2NC
RUN/STOP switch
n
works in parallel with the RUN-input terminal
o
.
Please refer to table 3.2.
During remote operation the FX
2NC
RUN/STOP status is determined by the most
recently operated control.
E.g. If the RUN/STOP switch is in RUN and a remote STOP is made from a personal
computer the RUN/STOP switch must be switched to STOP then back to RUN to
switch the MPU back to RUN mode.