FX2NC Series Programmable Controllers Installation notes 3.
3-6
3.3 General specifications
*1 Do not use the PLC under pressure higher than the atmospheric pressure. Doing so may
damage the PLC.
Table 3.3 :General Specifications
Item Description
Operating Temperature 0 to 55 °C (32 to 131 °F)
Storage Temperature -20 to 70 °C (-4 to 158 °F)
Operating Humidity 35 to 85% Relative Humidity, No condensation
storage Humidity 35 to 90% Relative Humidity, No condensation
Vibration Resistance
- Direct Mounting
10 - 57 Hz: 0.075 mm Half Amplitude
57 - 150 Hz: 9.8 m/s
2
Acceleration
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
Vibration Resistance
- DIN rail Mounting
10 - 57 Hz: 0.035 mm Half Amplitude
57 - 150 Hz: 4.9 m/s
2
Acceleration
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
Shock Resistance
147m/s
2
Acceleration, Action Time: 11 ms
3 times by half-sine pulse in each direction X, Y, and Z
Noise Immunity 1000 Vp-p, 1microsecond, 30 - 100 Hz, tested by noise simulator
Dielectric Withstand Voltage 500 V AC > 1 min, tested between all points, terminals and ground
Insulation Resistance 5 M
> at 500 V DC, tested between all points, terminals and ground
Ground Class D (100
or less)
Working atmosphere Free from corrosive or flammable gas and excessive conductive dust
Working altitude
<2000m