FX2NC Series Programmable Controllers Outputs 6.
6-2
6.1.1 Response times
OFF times increase as the load current decreases.
For improved response times use a 'dummy' resistor, see Figure 6.1. If a response time of 0.5
ms or better is required when using 'light loads' use a 'dummy' resistor and ensure the signal
line has a current greater than 60mA/24V DC.
Figure 6.1 :Dummy load
COM1
Y
Dummy
load
Load
5 to 30V DCSink
FX
2NC
Main unit
FX
2NC
Extention block
FX
0N
, FX
2N
Extention block