FX2NC Series Programmable Controllers Introduction 1.
1-22
Judgment form
a) 5V DC control current capacity check
b) Input/output point connection upper limit check
If all the above conditions are met, the extension and special function blocks can be con-
nected to the base block.
If one of the above conditions is not met, reduce the number of input/output points or
number of blocks, or change the types of blocks to be connected.
5V DC current capacity of main unit
(value shown in Sec. 1.5.2): mA
Total current consumption of all connected blocks
(value written in calculation form): mA
n
r
Input point connection
upper limit : 184 points
Input points of main unit
(value shown in Sec. 1.5.2):
points
Total input points of all
connected blocks (value
written in calculation form):
points
+ =
points
Output point
connection upper limit:
184 points
Output points of main unit
(value shown in Sec. 1.5.2):
points
Total output points of all
connected blocks (value
written in calculation form):
points
+ =
points
Input/output point
connection upper limit:
256 points
Input/output points of main unit
(value shown in Sec. 1.5.2):
points
Total input/output points of all
connected blocks (value
written in calculation form):
points
+ =
points
o
p
q
s
t
v