Loading...
329
APPENDICES
A
Appendix 1 Error Codes
Appendix 1.4 List of error codes (2000 to 2999)
2011
[BASE LAY ERROR]
The QA1S3B, QA1S5B, QA1S6B,
QA1S6ADP+A1S5B/A1S6B, QA6B, or
QA6ADP+A5B/A6B was used as the base
unit.
Collateral information
Common information: Base No.
Individual information: -
Diagnostic timing
At power-on/At reset
Do not use the QA1S3B, QA1S5B,
QA1S6B, QA1S6ADP+A1S5B/A1S6B,
QA6B, or QA6ADP+A5B/A6B as the
base unit.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Q00J/Q00/Q01
QnPH
QnPRH
QnU
2012
[BASE LAY ERROR]
The GOT is bus-connected to the main base unit
of the redundant system.
The following errors were detected in the
redundant system.
The base unit other than the Q6WRB is
connected to the extension stage No.1.
The base unit is connected to any one of the
extension stages No.2 to No.7, although the
Q6WRB does not exist in the extension stage
No.1.
The other system CPU module is incompatible
with the extension base unit.
The Q5B, QA1S5B, QA1S6B,
QA1S6ADP+A1S5B/A1S6B, QA6B or
QA6ADP+A5B/A6B is connected.
The number of slots of the main base unit for
both systems is different.
Information of the Q6WRB cannot be read
correctly.
Collateral information
Common information: Base No.
Individual information: -
Diagnostic ti
ming
At power-on/At reset
Remove the bus connection cable for the
GOT connected to the main base unit.
•Use the Q6WRB (fixed to the extension
stage No.1).
Use the redundant CPU compatible with
the extension base unit for the other
system.
Do not use the Q5B, QA1S5B,
QA1S6B,
QA1S6ADP+A1S5B/A1S6B, QA6B,
or QA6ADP+A5B/A6B as the base unit.
Use the main base unit which has the same
number of slots.
The cause is a hardware failure of the
Q6WRB. Please consult your local
Mitsubishi representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
2013
[BASE LAY ERROR]
Stage number of the Q6WRB is recognized as
other than extension stage No.1 in the redundant
system.
Collateral information
Common information: Base No.
Individual information: -
Diagnostic timing
At power-on/At reset
The cause is a hardware failure of the
Q6WRB. Please consult your local
Mitsubishi representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
2014
[BASE LAY ERROR]
The branch module on the block before the
LA1S5B is connected on the left of the END
cover.
Collateral information
Common information: Module No. (Block No.)
Individual information: -
Diagnostic timing
At power-on/At reset
Replace the LA1S5B with the LA1S6B.
Connect the branch module on the
LA1S5B on the right of the CPU module
or the extension module.
RUN: Off
ERR.:Flashing
CPU Status:Stop
LCPU
2020
[EXT.CABLE ERR.]
The following errors were detected in the
redundant system.
At power-on/reset, the standby system has
detected the error in the path between the
control system and the Q6
WRB.
The standby system detected an error in the
path to the Q6WRB in the END processing.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
At power-on/At reset/When an END instruction
executed
Check to see if the extension cable between
the main base unit and the Q6WRB is
connected correctly. If not, connect it after
turning OFF the main base unit where the
extension cable will be connected.
If the cable is properly connected, the cause
is a hardware failure of the CPU module,
Q6WRB, or extension cable. Please consult
your local Mitsubishi representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding