359
APPENDICES
A
Appendix 1 Error Codes
Appendix 1.5 List of error codes (3000 to 3999)
3003
[PARAMETER ERROR]
The automatic refresh range of the multiple CPU
system exceeded the file register capacity.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
When an END instruction or a COM instruction
executed
Change the file register file for the one that
the entire target range can be refreshed.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
QnU
[PARAMETER ERROR]
The number of device points set in the Device tab
of "PLC Parameter" is outside the range of the
specifications of the CPU module.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN/At writing to
programmable controller
Read the individual information of the error
using the programming tool to identify the
numeric value (parameter No.). Check the
parameters corresponding to the value,
and correct them as necessary.
If the error occurs even after the
parameters are corrected, the cause is a
failure of the program memory, memory
card, or SD memory card of the CPU
module. Please consult your local
Mitsubishi representative.
QCPU
LCPU
[PARAMETER ERROR]
The setting of the CC-Link IE Field Network Basic
refresh range crosses over the boundary between
the internal user device and the extended data
register (D) or extended link register (W).
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN/At writing to
programmable controller
Set the refresh range so that it does not cross
over the boundary between the internal user
device and the extended data register (D) or
extended link register (W).
QnUDV
LCPU
[PARAMETER ERROR]
The CC-Link IE Field Network Basic refresh range
exceeded the file register capacity.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN/At writing to
programmable controller/When an END
instruction or a COM instruction executed
Change the file register file for the one that
the entire target range can be refreshed.
Increase the file register capacity, or
change the refresh settings.
QnUDV
LCPU
3004
[PARAMETER ERROR]
The parameter file is incorrect.
Alternatively, the contents of the file are not
parameters.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN/At writing to
programmable controller
Ensure that the parameter file version is
***.QPA and the file contents are parameters.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QCP
U
LCPU
3005
[PARAMETER ERROR]
The contents of the parameter are broken.
Collateral information
Common information: File name/Drive name
Individual information: Parameter number
Diagnostic timing
At power-on/At reset/STOP RUN
Read the individual information of the error
using the programming tool to identify the
numeric value (parameter No.). Check the
parameters corresponding to the value,
and correct them as necessary.
Write the modified parameter items to the
CPU module again, and power-on the
programmable controller or reset the CPU
module.
If the same error occurred, the cause is a
hardware failure. Please consult your local
Mitsubishi representative.
RUN: Off
ERR.:Flashing
CPU Status:Stop
Qn(H)
QnPH
QnPRH
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU

Table of Contents