394
6020
[OPE. MODE DIFF.]
At power-on/reset, the RUN/STOP switch settings
of the control system and standby system are not
the same in a redundant system. (This can be
detected from the control system or standby
system of the redundant system.)
Collateral information
Common information: -
Individual information: -
Diagnostic timing
At power-on/At reset
Set the RUN/STOP switches of the control
system and standby system to the same
setting.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
6030
[UNIT LAY. DIFF.]
In a redundant system, the module configuration
differs between the control system and standby
system.
The network module mode setting differs
between the two systems. (This can be detected
from the control system or standby system of
the redundant system.)
Collateral information
Common information: Module No.
Individual information: -
Diagnostic timing
At power-on/At reset/At tracking cable
connection/At operation mode change
Match the module configurations of the
control system and standby system.
In the redundant setting of "Network
parameter", match the mode setting of
System B to that of System A.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
6035
[UNIT LAY. DIFF.]
In a redundant system, the CPU module model
name differs between the control system and
standby system. (This can be detected from the
standby system of the redundant system.)
Collateral information
Common information: -
Individual information: -
Diagnostic timing
At power-on/At reset/At tracking cable
connection/At operation mode change
Match the model names of the control system
and standby system.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
6036
[UNIT LAY. DIFF.]
A difference in the remote I/O configuration of the
MELSECNET/H multiplexed remote I/O network
between the control system and standby system of
a redundant system was detected. (This can be
detected from the control system or standby
system of the redundant system.)
Collateral information
Common information: Module No.
Individual information: -
Diagnostic timing
Always
Check the network cables of the
MELSECNET/H multiplexed remote I/O
network for disconnection.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
6040
[CARD TYPE DIFF.]
In the redundant system, the memory card
insertion status (inserted/not inserted) differs
between the control system and standby system.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
At power-on/At reset
Match the memory card insertion status
(inserted/not inserted) of the control system
and standby system.
RUN: Off
ERR.:Flashing
CPU S
tatus:Stop
QnPRH
6041
[CARD TYPE DIFF.]
In the redundant system, the memory card type
differs between the control system and standby
system.
Collateral information
Common information: -
Individual information: -
Diagnostic timing
At power-on/At reset
Match the memory card types of the control
system and standby system.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU