394
6020
[OPE. MODE DIFF.]
At power-on/reset, the RUN/STOP switch settings
of the control system and standby system are not
the same in a redundant system. (This can be
detected from the control system or standby
system of the redundant system.)
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• At power-on/At reset
Set the RUN/STOP switches of the control
system and standby system to the same
setting.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
6030
[UNIT LAY. DIFF.]
• In a redundant system, the module configuration
differs between the control system and standby
system.
• The network module mode setting differs
between the two systems. (This can be detected
from the control system or standby system of
the redundant system.)
■Collateral information
• Common information: Module No.
• Individual information: -
■Diagnostic timing
• At power-on/At reset/At tracking cable
connection/At operation mode change
• Match the module configurations of the
control system and standby system.
• In the redundant setting of "Network
parameter", match the mode setting of
System B to that of System A.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
6035
[UNIT LAY. DIFF.]
In a redundant system, the CPU module model
name differs between the control system and
standby system. (This can be detected from the
standby system of the redundant system.)
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• At power-on/At reset/At tracking cable
connection/At operation mode change
Match the model names of the control system
and standby system.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
6036
[UNIT LAY. DIFF.]
A difference in the remote I/O configuration of the
MELSECNET/H multiplexed remote I/O network
between the control system and standby system of
a redundant system was detected. (This can be
detected from the control system or standby
system of the redundant system.)
■Collateral information
• Common information: Module No.
• Individual information: -
■Diagnostic timing
• Always
Check the network cables of the
MELSECNET/H multiplexed remote I/O
network for disconnection.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
6040
[CARD TYPE DIFF.]
In the redundant system, the memory card
insertion status (inserted/not inserted) differs
between the control system and standby system.
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• At power-on/At reset
Match the memory card insertion status
(inserted/not inserted) of the control system
and standby system.
RUN: Off
ERR.:Flashing
CPU S
tatus:Stop
QnPRH
6041
[CARD TYPE DIFF.]
In the redundant system, the memory card type
differs between the control system and standby
system.
■Collateral information
• Common information: -
• Individual information: -
■Diagnostic timing
• At power-on/At reset
Match the memory card types of the control
system and standby system.
RUN: Off
ERR.:Flashing
CPU Status:Stop
QnPRH
Error
code
Error and cause Corrective action
LED status,
CPU status
Corresponding
CPU