7 - 44
7 OPERATION CONTROL PROGRAMS
F/FS G
7.7.5 Signed 64-bit floating-point value conversion : FLOAT
Format FLOAT(S) Number of basic steps 2
[Usable data]
Usable Data
Word device Constant
Setting
data
Bit device
16-bit
integer
type
32-bit
integer
type (L)
64-bit
floating
point
type (F)
Coasting
timer
16-bit
integer
type (K/H)
32-bit
integer type
(K/H, L)
64-bit
floating
point
type (K)
Calculation
expression
Bit
conditional
expression
Comparison
conditional
expression
(S) —
— —
: Usable
[Setting data]
Setting data Description Data type of result
(S)
Data which will be converted into signed 64-bit
floating-point value
64-bit floating-point type
[Functions]
(1) The data specified with (S) is converted into a signed 64-bit floating-point value.
(2) If (S) is a 64-bit floating-point type, its value is returned unchanged, with no
conversion processing performed.
[Errors]
(1) An operation error will occur if:
• (S) is an indirectly specified device and its device No. is outside the range.
[Program examples]
(1) Program which converts the data of D0L into a signed 64-bit floating-point value
and substitutes the result to #0F
#0F = FLOAT(D0L)
#3 #2
K-1.0
#1 #0
D1
K-1L
D0
(HFFFFFFFF)