67
Parameter List
Parameter List
4
PARAMETERS
Motor constants
80
Motor capacity
0.4 to 55kW, 9999/
0 to 3600kW, 9999
*2
0.01/0.1kW *2 9999
140,
181
81
Number of motor poles
2, 4, 6, 8, 10, 12, 14, 16,
18, 20, 9999
1 9999
140,
181
82
Motor excitation current
0 to 500A, 9999/
0 to 3600A, 9999
*2
0.01/0.1A
*2
9999 181
83 Motor rated voltage 0 to 1000V 0.1V 400V 181
84 Rated motor frequency 10 to 120Hz 0.01Hz 50Hz 181
89
Speed control gain (magnetic flux vector)
0 to 200%, 9999
0.1% 9999 140
90
Motor constant (R1)
0 to 50Ω, 9999/
0 to 400mΩ, 9999
*2
0.001Ω/
0.01mΩ
*2
9999 181
91
Motor constant (R2)
0 to 50Ω, 9999/
0 to 400mΩ, 9999
*2
0.001Ω/
0.01mΩ
*2
9999 181
92 Motor constant (L1)
0 to 50
Ω
(0 to 1000mH), 9999
/
0 to 3600m
Ω
(0 to 400mH), 9999
*2
0.001
Ω
(0.1mH)/
0.01m
Ω
(0.01mH)
*2
9999 181
93
Motor constant (L2)
0 to 50
Ω
(0 to 1000mH), 9999
/
0 to 3600m
Ω
(0 to 400mH), 9999
*2
0.001
Ω
(0.1mH)/
0.01m
Ω
(0.01mH)
*2
9999 181
94 Motor constant (X)
0 to 500
Ω
(0 to 100%), 9999/
0 to 100
Ω
(0 to 100%), 9999
*2
0.01Ω (0.1%)/
0.01Ω (0.01%)
*2
9999 181
95
Online auto tuning selection 0 to 2
1 0 191
96 Auto tuning setting/status 0, 1, 101 1 0 181
Adjustable 5 points V/F
100 V/F1(first frequency) 0 to 400Hz, 9999 0.01Hz 9999 159
101
V/F1(first frequency voltage) 0 to 1,000V
0.1V 0V 159
102
V/F2(second frequency) 0 to 400Hz, 9999
0.01Hz 9999 159
103
V/F2(second frequency voltage) 0 to 1,000V
0.1V 0V 159
104
V/F3(third frequency) 0 to 400Hz, 9999
0.01Hz 9999 159
105
V/F3(third frequency voltage) 0 to 1,000V
0.1V 0V 159
106
V/F4(fourth frequency) 0 to 400Hz, 9999
0.01Hz 9999 159
107 V/F4(fourth frequency voltage) 0 to 1,000V 0.1V 0V 159
108 V/F5(fifth frequency) 0 to 400Hz, 9999 0.01Hz 9999 159
109 V/F5(fifth frequency voltage) 0 to 1,000V 0.1V 0V 159
Third functions
110
Third acceleration/deceleration time 0 to 3600/360s, 9999
0.1/0.01s 9999 167
111
Third deceleration time 0 to 3600/360s, 9999
0.1/0.01s 9999 167
112
Third torque boost 0 to 30%, 9999
0.1% 9999 138
113
Third V/F (base frequency) 0 to 400Hz, 9999
0.01Hz 9999 153
114
Third stall prevention operation current 0 to 220%
0.1% 150% 144
115
Thrid stall prevention operation
frequency
0 to 400Hz 0.01Hz 0 144
116
Third output frequency detection 0 to 400Hz
0.01Hz 50Hz 237
PU connector
communication
117
PU communication station number 0 to 31
1 0 320
118
PU communication speed 48, 96, 192, 384
1 192 320
119
PU communication stop bit length 0, 1, 10, 11
1 1 320
120 PU communication parity check 0, 1, 2 1 2 320
121 Number of PU communication retries 0 to10, 9999 1 1 320
122
PU communication check time interval 0, 0.1 to 999.8s, 9999
0.1s 9999 320
123
PU communication waiting time setting 0 to 150ms, 9999
1 9999 320
124
PU communication CR/LF selection 0, 1, 2
1 1 320
⎯
125
Terminal 2 frequency setting gain
frequency
0 to 400Hz
0.01Hz 50Hz 282
⎯
126
Terminal 4 frequency setting gain
frequency
0 to 400Hz
0.01Hz 50Hz 282
Func-
tion
Parameter
Name Setting Range
Minimum
Setting
Increments
Initial Value
Refer
to
Page
Customer
Setting