68
Parameter List
Parameter List
PID operation
127
PID control automatic switchover
frequency
0 to 400Hz, 9999 0.01Hz 9999 348
128
PID action selection
10, 11, 20, 21, 50, 51, 60,
61, 70, 71, 80, 81, 90, 91,
100, 101
1 10 348
129
PID proportional band 0.1 to 1000%, 9999
0.1% 100% 348
130
PID integral time 0.1 to 3600s, 9999
0.1s 1s 348
131
PID upper limit 0 to 100%, 9999
0.1% 9999 348
132
PID lower limit 0 to 100%, 9999
0.1% 9999 348
133 PID action set point 0 to 100%, 9999 0.01% 9999 348
134 PID differential time 0.01 to 10.00s, 9999 0.01s 9999 348
Electronic bypass
135 Electronic bypass sequence selection 0, 1 1 0 356
136
MC switchover interlock time 0 to 100s
0.1s 1s 356
137
Start waiting time 0 to 100s
0.1s 0.5s 356
138
Bypass selection at an alarm 0, 1
1 0 356
139
Automatic switchover frequency from
inverter to bypass operation
0 to 60Hz, 9999
0.01Hz 9999 356
Backlash
measures
140
Backlash acceleration stopping
frequency
0 to 400Hz
0.01Hz 1Hz 170
141
Backlash acceleration stopping time 0 to 360s
0.1s 0.5s 170
142
Backlash deceleration stopping
frequency
0 to 400Hz 0.01Hz 1Hz 170
143
Backlash deceleration stopping time 0 to 360s
0.1s 0.5s 170
⎯ 144
Speed setting switchover
0, 2, 4, 6, 8, 10, 102,
104, 106, 108, 110
1 4 242
PU
145
PU display language selection 0 to 7
1 1 381
Current detection
148 Stall prevention level at 0V input 0 to 220% 0.1% 150% 144
149 Stall prevention level at 10V input 0 to 220% 0.1% 200% 144
150
Output current detection level 0 to 220%
0.1% 150% 239
151
Output current detection signal delay
time
0 to 10s
0.1s 0s 239
152 Zero current detection level 0 to 220% 0.1% 5% 239
153 Zero current detection time 0 to 1s 0.01s 0.5s 239
⎯
154
Voltage reduction selection during stall
prevention operation
0, 1
1 1 144
⎯ 155
RT signal function validity condition
selection
0, 10
1 0 226
⎯ 156
Stall prevention operation selection 0 to 31, 100, 101
1 0 144
⎯
157 OL signal output timer 0 to 25s, 9999 0.1s 0s 144
⎯
158
AM terminal function selection
1 to 3, 5 to 14, 17, 18,
21, 24, 32 to 34, 50,
52, 53, 70
1 1 244
⎯
159
Automatic switchover frequency range
from bypass to inverter operation
0 to 10Hz, 9999 0.01Hz 9999 356
⎯
160
User group read selection 0, 1, 9999 1 0 299
⎯ 161
Frequency setting/key lock operation
selection
0, 1, 10, 11
1 0 381
Automatic restart
functions
162
Automatic restart after instantaneous
power failure selection
0, 1, 2, 10, 11, 12
1 0 254
163 First cushion time for restart 0 to 20s 0.1s 0s 254
164
First cushion voltage for restart 0 to 100%
0.1% 0% 254
165
Stall prevention operation level for
restart
0 to 220%
0.1% 150% 254
Current detection
166
Output current detection signal
retention time
0 to 10s, 9999
0.1s 0.1s 239
167
Output current detection operation
selection
0, 1 1 0 239
Func-
tion
Parameter
Name Setting Range
Minimum
Setting
Increments
Initial Value
Refer
to
Page
Customer
Setting