81
DRIVE THE MOTOR
3
Parameter list
Parameter List
Remote setting function
59
Remote function
selection
10
0
RH, RM, RL signal
function
Frequency setting
storage function

Multi-speed setting
1 Remote setting Yes
2 Remote setting No
3 Remote setting
No (Turning STF/
STR OFF clears
remotely-set
frequency.)
Energy saving
control selection
60
Energy saving
control selection
10
0 Normal operation mode

9 Optimum excitation control mode
Retry function at fault occurrence
65
Retry selection
1 0 0 to 5 A fault for retry can be selected. 
67
Number of retries
at fault occurrence
10
0 No retry function

1 to 10
Number of retries at fault occurrence.
A fault output is not provided during retry
operation.
101 to 110
Number of retries at fault occurrence. (The
setting value of minus 100 is the number of
retries.) A fault output is provided during
retry operation.
68
Retry waiting time
0.1s 1s 0.1 to 600s
Waiting time from when an inverter fault
occurs until a retry is made.

69
Retry count
display erase
100
Clear the number of restarts succeeded by
retry.

——
66
Refer to Pr.22, Pr.23.
67 to 69
Refer to Pr.65.
70
Refer to Pr.30.
Function
Parameter
Name
Incre-
ments
Initial
Value
Range Description
Parameter
Copy
Parameter
Clear
All Parameter
Clear
Related
Parameter
V/F
V/F
V/F