84
Parameter list
Offline auto tuning
82
Motor excitation
current
0.01A 9999
0 to 500A
Set motor excitation current (no load
current)
×
9999
Uses the Mitsubishi motor (SF-JR, SF-HR,
SF-JRCA, SF-HRCA) constants
83
Rated motor
voltage
0.1V
200V/
400V
0 to 1000V
Rated motor voltage (V).
* The initial value differs according to the
voltage class. (100V, 200V class/400V class)

84
Rated motor
frequency
0.01Hz 60Hz
10 to
120Hz
Rated motor frequency (Hz). 
90
Motor constant
(R1)
0.001Ω 9999
0 to 50Ω
Tuning data (The value measured by
offline auto tuning is automatically set.)
×
9999
Use constants of the Mitsubishi motor (SF-
JR, SF-HR, SF-JRCA, SF-HRCA)
96
Auto tuning
setting/status
10
0 Offline auto tuning is not performed
×
11
For General-purpose magnetic flux vector
control
Offline auto tuning is performed without
motor running(motor constant (R1) only)
21
Offline auto tuning for V/F control
(automatic restart after instantaneous
power failure (with frequency search))
( Refer to Chapter 4 of the Instruction
Manual (Applied))
Function
Parameter
Name
Incre-
ments
Initial
Value
Range Description
Parameter
Copy
Parameter
Clear
All Parameter
Clear