EasyManua.ls Logo

Mitsubishi FREQROL-Z200-UL

Mitsubishi FREQROL-Z200-UL
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Setting
Correction
0 Speed (frequency) is not corrected (initial setting) .
9. ,,
1 Speed (frequency) is corrected.
Note: The signal should be input through terminal 1 K or 1 E .
PWM MODE
PWM mode
q q
By changing carrier frequency (hertz) ,
motor sound and vibration can be reduced.
80Hz per graduation change.
One of 16 carrier frequencies can be selected.
Note: Initial setting is 3 .
SPEED DISPLAY
Speed display .a 0
Motor speed can be directly displayed in MONITOR mode in terms of rpm or
m/min, instead of inverter output frequency.
Displayed motor speed is that converted from inverter output frequency, and not
always equal to true speed.
Setting 0 Inverter output frequency (Hz) is displayed (initial setting) .
Setting
2 - 10
(Number of
motor poles
is input.)
Motor speed is displayed ,in rpm. (Note
11
Setting
11 - 9998
Speed of load is displayed. (Note 2 >
Ex.: 1 . Display of ,mot.or speed (r-pm)
When 4 -pole motor is driven by the inverter.
Notes: 1 . Setting should be an even number (motor poles) within the range
0
0
-ml-