FX1S Series Programmable Controller Introduction 1
1-8
1.4.2 Limits of Expansion
The following conditions cannot be accomplished the FX
1S
Series PLC:
- The use of Special Function Blocks.
- Supply a 5V DC service supply.
-Use FX
1N
-422-BD + FX-2PIF.
- Use the FX
1N
-5DM and the FX-10DM concurrently.
- Use more than one FX-10DM at the same time. For example, the configuration
FX-10DM + (FX
1N
-422-BD + FX-10DM) is not allowed.
1.5 EEProm Backup Data
FX
1S
existing data will be kept for 5 minutes during power down before the data is lost.
The capacitor backed memory will retain programs for 10 days and the capacitor requires 30
minutes to recharge upon powerup.