3 ETHERNET INTERFACE MODULE REPLACEMENT
3 - 9
*4 Communications using pairing open
On the Q series, the pairing open setting of connection No.8 is not possible.
(Connection No.8 is pairing for reception, and connection No.1 is pairing for transmission.)
When the pairing open setting of connection No.8 has been made, change the sequence program.
On the Q series, the pairing open settings of connection No.1 to 7, and 9 to 15 are possible.
*5 Open processing
When "Operational settings" - "Initial timing" in GX Developer is set to "Always wait for OPEN", the sequence program using
dedicated instruction (OPEN/CLOSE) is not required.