EasyManua.ls Logo

Mitsubishi PLH-4AAK - Thermistor Characteristic Graph; Thermistor for Drain Sensor; Thermistor for Lower Temperature

Mitsubishi PLH-4AAK
86 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
45
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
< Thermistor for lower temperature >
Temperature (:)
Resistance (K")
<Thermistor Characteristic graph>
Room temperature thermistor(TH1)
Pipe temperature thermistor/liquid(TH2)
Thermistor R0=15k' ±3%
Fixed number of B=3480 ± 2%
Rt=15exp { 3480( ) }
0: 15k'
10: 9.6k'
20: 6.3k'
25: 5.4k'
30: 4.3k'
40: 3.0k'
Thermistor R0=6.0k' ±5%
Fixed number of B=3390 ±2%
Rt= 6 exp { 3390( ) }
0: 6.0k'
10: 3.9k'
20: 2.6k'
25: 2.2k'
30: 1.8k'
40: 1.3k'
60: 0.6k'
Thermistor for
lower temperature
1
273+t
1
273
1
273+t
1
273
-20 0 20406080
< Thermistor for drain sensor >
Temperature (:)
0
1
2
3
4
5
6
7
8
9
10
Resistance (K")
Thermistor for
drain sensor
OC360--2.qxp 06.2.24 1:55 PM Page 45