Appendix 6 Precautions for Using Serial Communication Module
Appendix 6.1 CSET Instruction
APPENDICES
The program example of clearing receive data is shown in Diagram App.26.
(For the I/O signal is X/Y80 to X/Y9F)
* 1: When using the Q series C24 (function version A), add the dotted line to the sequence program.
* 2: Communicate data when M19 is ON
Diagram App.26 Program Example
0
PLS M15
3
M15
SET M16
SET M17
5
M16 M17
TO H8 H0A8 K1 K1
M18
*1
*1
X83 X84
*1
RST M16
RST M17
RST M18
SET M18
T100
K10
H
=D0K0
18
M17
T100
FROM H8 H0A8 D0 K1
30
M18
M19
37
M16 M17
M18
X23
M11
M12
*2
Accepts the receive
data clear request.
Requests the receive
data clear.
Turns ON the receive
data clear completion flag.
Reads the receive
data clear status.
Resets the receive
data clear flag.
Makes the 100ms data
communication to be
disabled after “1” is
changed into “0”.