EasyManuals Logo

Moxa Technologies ioLogik 2542 User Manual

Moxa Technologies ioLogik 2542
102 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
ioLogik 2500 Series Overview
1-8
Flow Control:
None, RTS/CTS, XON/XOFF
Baudrate:
300 to 115200 bps
Protocols:
Modbus/RTU (master/gateway), serial tunnel mode (client/server)
Physical Characteristics
Wiring:
I/O cable, 14 AWG (max.)
Dimensions:
61 x 157 x 115 mm (2.4 x 6.18 x 4.53 in)
Weight: Under 1265 g (2.79 lb)
Mounting:
DIN rail (standard), wall (optional)
Storage
Expansion Slot:
Up to 32 GB microSD™ memory card (SDHC compatible)
Note: For units operating in extreme temperatures, industrial
-grade, wide-temperature SD cards are
required.
Environmental Limits
Operating Temperature:
Standard Models:
-10 to 60°C (14 to 140°F)
Wide Temp. Models:
-30 to 70°C (-22 to 158°F)
Storage Temperature:
-40 to 85°C (-40 to 185°F)
Ambient Relative Humidity: 5 to 95% (non-condensing)
Shock:
IEC 60068-2-27
Vibration:
IEC 60068-2-6
Altitude:
Up to 2000 m
Note: Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
Standards and Certifications
Safety:
UL 508
EMC:
EN 61000-6-2/6-4
EMI:
CISPR 32, FCC Part 15B Class A
EMS:
IEC 61000
-4-2 ESD: Contact: 4 kV; Air: 8 kV
IEC 61000
-4-3 RS: 80 MHz to 1 GHz: 3 V/m
IEC 61000
-4-4 EFT: Power: 1 kV; Signal: 0.5 kV
IEC 61000
-4-5 Surge: Power 2 kV
IEC 61000
-4-6 CS: 3 V
IEC 61000
-4-8
Radio:
R&TTE: EN 62311, EN 300 328, EN 301 489-1, EN 301 489-17, EN 301 893; NCC; VCCI
Hazardous Location:
Class 1 Division 2; ATEX Zone 2
Green Product:
RoHS, CRoHS, WEEE
Note: Please check Moxa’s website for the most up
-to-date certification status.
Warranty
Warranty Period:
5 years
Details: See www.moxa.com/warranty
ioLogik 2512 HSPA/GPRS/WLAN Specifications
Inputs and Outputs
Digital Inputs:
8 channels
Configurable DIOs (by software): 8 channels
Isolation:
3k VDC or 2k Vrms
Digital Input
Sensor Type:
Wet Contact (NPN or PNP) and Dry Contact
I/O Mode:
DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Moxa Technologies ioLogik 2542 and is the answer not in the manual?

Moxa Technologies ioLogik 2542 Specifications

General IconGeneral
BrandMoxa Technologies
ModelioLogik 2542
CategoryI/O Systems
LanguageEnglish

Related product manuals