EasyManua.ls Logo

MPP Solar 3KVA - Page 15

MPP Solar 3KVA
29 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13
UPS
If selected, the transfer time is within
10ms between battery mode and line
mode
05
Battery type
AGM (default)
Flooded
User-Defined
If “User-Defined” is selected, battery
charge voltage and low DC cut-off
voltage can be set up in program 26,
27 and 29.
06
Auto restart when overload
occurs
Restart disable
(default)
Restart enable
07
Auto restart when over
temperature occurs
Restart disable
(default)
Restart enable
09
Output frequency
50Hz (default)
60Hz
11
Maximum utility charging
current
15A(default)
25A
12
Setting voltage point back
to utility source when
selecting “SBU priority” or
“Solar first” in program 01.
22.0V
22.5V
23.0V (default)
23.5V
24.0V
24.5V
25.0V
25.5V
13
Setting voltage point back
to battery mode when
selecting “SBU priority” or
“Solar first” in program 01.
Battery fully charged
24V
24.5V
25V

Related product manuals