7. TROUBLE SHOOTING
Problem
LCD/LED/Buzzer
Explanation / Possible cause
What to do
Unit shuts down
automatically
during startup
process.
LCD/LEDs and buzzer
will be active for 3
seconds and then
complete off.
The battery voltage is too low
(<1.91V/Cell)
1. Charge battery.
2. Replace battery.
No response after
power on.
No indication.
1. The battery voltage is far too
low. (<1.4V/Cell)
2. Battery polarity is connected
reversed.
1. Check if batteries and the
wiring are connected well.
2. Charge battery.
3. Replace battery.
Buzzer beeps
continuously and
red LED is on.
Fault code 07
Overload error. The inverter is
overload 110% and time is up.
Reduce the connected load by
switching off some
equipment.
Fault code 05
Output short circuited.
Check if wiring is connected
well and remove abnormal
load.
Temperature of internal converter
component is over 120°C.
Check whether the air flow of
the unit is blocked or whether
the ambient temperature is
too high.
Fault code 02
Internal temperature of inverter
component is over 100°C.
Fault code 03
The battery voltage is too high.
Check if spec and quantity of
batteries are meet
requirements.
Fault code 01
Fan fault
Replace the fan.
Fault code 06
Output abnormal (Inverter voltage
below than 190Vac or is higher
than 260Vac)
1. Reduce the connected
load.
2. Return to repair center
Fault code 08/09
Internal components failed.
Return to repair center.