14
Appendix: Approximate Back-up Time Table
Model
Load (VA)
Backup Time @ 24Vdc 100Ah (min)
Backup Time @ 24Vdc 200Ah (min)
2KVA
200
766
1610
400
335
766
600
198
503
800
139
339
1000
112
269
1200
95
227
1400
81
176
1600
62
140
1800
55
125
2000
50
112
3KVA
300
449
1100
600
222
525
900
124
303
1200
95
227
1500
68
164
1800
56
126
2100
48
108
2400
35
94
2700
31
74
3000
28
67
Note: Backup time depends on the quality of the battery, age of battery and type of battery.