Fault
code no. Full designation Meaning Action
Setting parame-
ter no.
091 SS Release Speed Not
Reached
Runup speed not reached
(alarm configuration parame-
ter, see PR 2.8008.100 for
explanation). Start terminat-
ed.
Check for additional
messages. Recharge
battery. Engine un-
der load: Check fuel
supply; if no fault
detected, contact
Service.
2.1090.924
092 SS Starter Speed Not
Reached
Starter speed not reached
(alarm configuration parame-
ter, see PR 2.8008.100 for
explanation). Start terminat-
ed. Starter does not turn or
turns slowly.
Check for additional
messages. Recharge
battery. Engine un-
der load: Check fuel
supply; if no fault
detected, contact
Service.
2.1090.923
093 SS T-Preheat Preheating temperature too
low (limit value 2, alarm con-
figuration parameter, see PR
2.8008.100 for explanation).
Engine start inter-
lock is active as
coolant temperature
is too low for engine
start, preheating
necessary.
2.1090.922
094 LO T-Preheat Preheating temperature too
low (limit value 1, alarm con-
figuration parameter, see PR
2.8008.100 for explanation).
Engine start inter-
lock is active as
coolant temperature
is too low for engine
start, preheating
necessary.
2.1090.921
095 AL Prelubrication Fault Oil priming pressure not
reached (alarm configuration
parameter, see PR
2.8008.100 for explanation).
Contact Service. 2.1090.920
102 AL Fuel Cons. Counter
Defect
Electronic fault: Consump-
tion counter faulty (alarm
configuration parameter, see
PR 2.8008.100 for explana-
tion).
Replace engine gov-
ernor at next oppor-
tunity.
1.8004.624
104 AL Eng Hours Counter
Defect
Electronic fault: Hour meter
faulty (alarm configuration
parameter, see PR
2.8008.100 for explanation).
Replace engine gov-
ernor at next oppor-
tunity.
1.8004.623
118 LO ECU Power Supply
Voltage
Supply voltage too low (limit
value 1, alarm configuration
parameter, see PR
2.8008.100 for explanation).
Warning.
Check batteries and
charge as necessa-
ry; check generator.
2.0140.921
119 LOLO ECU Power Sup-
ply Voltage
Supply voltage too low (limit
value 2, alarm configuration
parameter, see PR
2.8008.100 for explanation).
Warning.
Check batteries and
charge as necessa-
ry; check generator.
2.0140.922
48 | Troubleshooting | MS15018/03E 2016-02