HM3Humidier
Example3
-Outdoortemperature:–20°C
-Outdoorhumidity:40%RH
-Airchanges:2perhour
-Desiredtemperature:22°C
-Desiredhumidity:50%RH
Maximumpermittedroomvolumeforeachmodel:
-HM32000upto270m
3
-HM35000upto675m
3
-HM310000upto1350m
3
Multipleunitsshouldbeusedifneeded.
Example4
-Outdoortemperature:–20°C
-Outdoorhumidity:40%RH
-Airchanges:2perhour
-Desiredtemperature:15°C
-Desiredhumidity:75%RH
Maximumpermittedroomvolumeforeachmodel:
-HM32000upto115m
3
-HM35000upto290m
3
-HM310000upto580m
3
Multipleunitsshouldbeusedifneeded.