HM3Humidier
10Simplieddimensioning
Thisisasimpliedmethodofestimatingtherequiredcapacity.
ContactyourMuntersrepresentativeformoreinformationandhelpwiththedimensioning.
0
10
20
30
40
50
60
70
80
90
100
20
12 14
16
18
22 24
26
28
30
%Rh
°C
Figure10.1Comfortzoneforhumansworking
Example1
-Outdoortemperature:0°C
-Outdoorhumidity:40%RH
-Airchanges:2perhour
-Desiredtemperature:22°C
-Desiredhumidity:50%RH
Maximumpermittedroomvolumeforeachmodel:
-HM32000upto290m
3
-HM35000upto720m
3
-HM310000upto1440m
3
Multipleunitsshouldbeusedifneeded.
Example2
-Outdoortemperature:0°C
-Outdoorhumidity:40%RH
-Airchanges:2perhour
-Desiredtemperature:15°C
-Desiredhumidity:75%RH
Maximumpermittedroomvolumeforeachmodel:
-HM32000upto125m
3
-HM35000upto315m
3
-HM310000upto625m
3
Multipleunitsshouldbeusedifneeded.
39SimplieddimensioningTEN-HM3-B1506