MG50&MG90
7Faulttracing
SymptomPossiblecauseCorrectiveaction
FailureoftheelectricalsupplyCheckpowersupplytotheunit.
Theunitwassettoautomaticmodeby
mistakewithnohumidistatconnected.
Humidistatfault(automaticmode).
Settomanualoperatingmodeandcheckthatthedehumidier
starts.Iftheunitstarts,theproblemprobablylieswiththe
humidistat.Checkthehumidistatbycheckingthatthe
dehumidierstartswhenthesetpointofthehumidistatis
lowered.Resetthehumidistatsetpointafterthecheck.
Calibratethehumidistatasnecessaryorreplaceit.
Thethermalprotectioninthefanmotorhas
beentriggered.
-Switchofftheunitanddisconnectthepowersupply
-Removetheconnectionpiecesforthehosesorductsandthe
ltercartridgeontheprocessand/orreactivationside.
-Checkthattheimpellerswhicharenowaccessiblerotate
freely.
Unithasstopped.
Thehigh-temperaturefusehasbeen
tripped.
Checkthattheltersandhosesorductsarenotcloggedand
resetthefuse.Beforethefusecanbereset,theunitmustbe
disconnectedfromthepowersourceandthenreconnected
onceithascooled.Theprimarycausesbehindtriggeringofthe
high-temperaturefuseare:
-Faultinthereactivationairow.
-Blockedlter,hoseorduct.
-Blockedimpeller.
Reactivationtemperatureistoolow.Checkthattheoriceplate(A)istted.
Thereactivationheaterisnotoperating.Checkthatthereactivationheaterisworkingbymeasuring
currentconsumption,seechapter8.4,Technicaldata.
ThereactivationairowisincorrectCheckthelterandanyhosesorductsforleakageorblockage.
Theuseofarestrictingangeincombinationwithwallpipes
canalsocauseanincorrectreactivationairow.
Lossofperformance:
Thedehumidieris
inoperationbutisnot
controllingthehumidity.
RotordrivemechanismfaultCheckthroughthedryairoutletthattherotorrotatesatapprox.
10revolutionsperhour.
Table7.1Faulttracinglist
17Faulttracing190TGB-1004–N1402