EasyManuals Logo

Munters MG50 User Manual

Munters MG50
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
MG50&MG90
4.3Connectionofductsandhoses
Followtheinstructionsbelowwhenattachingductsorexiblehosestotheairconnections.Theprocessand
reactivationairinletanddryairoutletcanbeconnectedtoaductsystemorbeusedwithfreeinletandoutlet.
Thewetairoutletmustalwaysbeconnectedtoaductorhose,whichmustbettedatadownwardangle
(awayfromthedehumidier)sothatcondensationisdrained.
Ductlengthmustbekeptasshortaspossibletominimisestaticpressureloss.
Allductandhoseconnectionsmustbeairtightandvapourtighttoensurefullperformance.
Thewetairductorhosemustbemountedatadownwardanglesothatcondensationcanbedrained.
Thewetairhoseorductmusthavesuitabledrainageatlowtemperaturestopreventpoolingof
condensate.Alternatively,condensationcanbeavoidedbyinsulatingtheductwithatleast25mmof
insulation.
Covertheductopeningforoutdoorairwithmeshtopreventbirdsandrodentsfromenteringtheunit.
Positiontheopeningsothatrainandsnowcannotentertheduct.
Thewetairductorhosemustbecorrosionresistantandabletowithstandtemperaturesupto70°C.
Thewetairisnormallytransportedoutdoors.Inlargepremiseswherethedehumidierisoutsideofthe
spacetobedehumidied,thewetaircanbeledawayneartheunit.Positiontheoutletsothatthewetair
doesnotblowtowardsmoisture-sensitiveobjects.
Theminimumdistancebetweenthereactivationinletorwetairoutletandthewallis0.5m.
Theltersforbothprocessandreactivationaircanbereplacedwithouthavingtodetachductsorhoses.
CA CA
CA
UTION! UTION!
UTION!
Ifthereisariskoffreezingtemperatures,thewetairductsmustbeinsulated.
NOTE!Noisereductioncanbeachievedbyconnectingductstothedehumidier.
4.4Hoselengthandoriceplateaffectstheairow
Wetair/reactivationair
Thedehumidierisequippedwithanoriceplate(A)inthewetairoutlet.Whenawallpipeisconnected
tothehose(see4.5,Mountingtheunitonthewall),oriftheexiblehoseorductislongerthan5m(max.10
m),theoriceplatemustberemoved.
Dryair/processair
Thehoseorductfordryandprocessaircanhaveatotallengthof10mbeforedehumidicationcapacityis
affected.Theconnectionpiece(B)makesitpossibletoconnectthedryairoutlettoahoseorductsystem.
7Installation190TGB-1004–N1402