4.3Connectionofductsandhoses
Followtheinstructionsbelowwhenattachingductsorexiblehosestotheairconnections.Theprocessand
reactivationairinletanddryairoutletcanbeconnectedtoaductsystemorbeusedwithfreeinletandoutlet.
Thewetairoutletmustalwaysbeconnectedtoaductorhose,whichmustbettedatadownwardangle
(awayfromthedehumidier)sothatcondensationisdrained.
Ductlengthmustbekeptasshortaspossibletominimisestaticpressureloss.
Allductandhoseconnectionsmustbeairtightandvapourtighttoensurefullperformance.
Thewetairductorhosemustbemountedatadownwardanglesothatcondensationcanbedrained.
Thewetairhoseorductmusthavesuitabledrainageatlowtemperaturestopreventpoolingof
condensate.Alternatively,condensationcanbeavoidedbyinsulatingtheductwithatleast25mmof
insulation.
Covertheductopeningforoutdoorairwithmeshtopreventbirdsandrodentsfromenteringtheunit.
Positiontheopeningsothatrainandsnowcannotentertheduct.
Thewetairductorhosemustbecorrosionresistantandabletowithstandtemperaturesupto70°C.
Thewetairisnormallytransportedoutdoors.Inlargepremiseswherethedehumidierisoutsideofthe
spacetobedehumidied,thewetaircanbeledawayneartheunit.Positiontheoutletsothatthewetair
doesnotblowtowardsmoisture-sensitiveobjects.
Theminimumdistancebetweenthereactivationinletorwetairoutletandthewallis0.5m.
Theltersforbothprocessandreactivationaircanbereplacedwithouthavingtodetachductsorhoses.
CA CA
CA
UTION! UTION!
UTION!
Ifthereisariskoffreezingtemperatures,thewetairductsmustbeinsulated.
NOTE!Noisereductioncanbeachievedbyconnectingductstothedehumidier.
4.4Hoselengthandoriceplateaffectstheairow
Wetair/reactivationair
Thedehumidierisequippedwithanoriceplate(A)inthewetairoutlet.Whenawallpipeisconnected
tothehose(see4.5,Mountingtheunitonthewall),oriftheexiblehoseorductislongerthan5m(max.10
m),theoriceplatemustberemoved.
Dryair/processair
Thehoseorductfordryandprocessaircanhaveatotallengthof10mbeforedehumidicationcapacityis
affected.Theconnectionpiece(B)makesitpossibletoconnectthedryairoutlettoahoseorductsystem.
7Installation190TGB-1004–N1402